CMS-MCC (Master Control Component)

  • Burner sequencer (FA1 Function)
  • 12 Digital Inputs, 9 digital Outputs, freely configurable
  • Input for flame scanner FFS07/08 (option)
  • Input for ionisation (option)
  • Firing rate input 4 - 20 mA / TPS or potentiometer,
    Output 4 - 20 mA internal firing rate
  • Codesys Soft-PLC with access to internal variables for
    non-failsafe extensions
  • Modbus TCP interface on-board (Ethernet)
  • Versions available:
    • Input 115/230 VAC Output 115/230 VAC
    • Input 24 VDC Output 115/230 VAC
    • Input 24 VDC Output 24 VDC

AES-TPS (Actuator Extension Component- Tree Point Step)

  • Compatible with ETAMATIC / FMS servomotors
  • 1 Module supports 2 TPS servomotors
  • Current output supports up to 0,5 A for each motor
  • Up to 5 AEC-TPS modules per system
  • Up to 10 servomotors per CMS system possible

AEC-VS (Actuator Extension Component- Vatiable Speed)

  • Module for frequency inverter of the combustion air fan or recirculation fan
  • Module for 4 - 20 mA motors, pneumatic actuators etc.
  • Up to10 AEC-VS per CMS system possible
  • VSD module with feedback input for Namur sensor,
    3-wire sensor and 4 - 20 mA output for ‘Fan ON‘,
    digital input for frequency inverter fault/status signal

SDI (Safe Digital Input)

  • 8 Inputs per module
  • All inputs are freely configurable
  • Available in alternative versions for 115/230 V and 24 VDC
  • Up to 6 digital input modules
  • Up to 60 digital inputs per CMS system possible

SDO (Safe Digital Output)

  • 8 Outputs per module
  • All outputs are freely configurable
  • Available in alternative versions for 115/230 VAC and 24 VDC
  • Up to 4 digital output modules
  • Up to 41 digital outputs per CMS system possible

SAI ( Safe Analogue Input)

  • ›3 Failsafe analogue inputs or 6 non-failsafe analogue inputs
    or any combination of it
  • ›All inputs are freely configurable to the functions
  • ›Inputs: 4 … 20 mA, 0 … 10 V impulse or digital
  • ›Up to 3 SAI per system
  • ›Up to 9 failsafe or 18 non-failsafe inputs
    per CMS system possible